Low in cost, yet packed with all the features needed for accurate, dependable service.
NULL-KOTE™ Circuitry – Makes the sensor immune to adverse effects from conductive coating build-up.
Ten-Year Warranty – The only level instruments available with this unique assurance of quality.
Easy-On Probe Connection – Automatically provides simple, fast installation and reliable operation without wires, connectors, or terminal strips. Simply screw probe into the housing.
Time-Delay Included –
0-30 second delay - no extra cost
Unique Status Indicator –
(two color) Shows presence or absence of material and also indicates power "on".
Heavy Duty Relay –
10A 115 Vac resistive contacts
High or Low Fail-Safe – Field selectable.
Explosion-Proof Housing –
Class I Groups C & D,
Class II Groups E, F, & G
NEMA 4
Wide Temperature Range –
Standard process temperature: -300 to 500°F (-184 to 260°C).
ROLLOCK™ PROBES –
No part of probe can fall into the process or be blown from mounting. No re-tightening of seals required.
PRINCO’s model L2000 radio frequency (RF) point level controller is truly an outstanding value.
It combines rugged construction, quick, easy installation and all the features you need for years of effective, accurate performance.
Operating on the RF impedance sensing principle, the L2000 will detect the presence (high level) or absence (low level) of a wide variety of materials. It may be made fail-safe in either high or low mode. It will operate in conjunction with process materials which range from low dielectric (insulating) products such as refined oils, to conductive slurries.
The L2000 incorporates PRINCO’s user-oriented features ... reliability, true coating cancellation capability, explosion-proof/weatherproof enclosures, RFI immunity, heavy duty relays, Easy-On Teflon/316SS probes and our unique 10-Year Warranty.
The L2000 has everything you need at a price no higher than the "also rans."
In tens of thousands of installations, spanning more than 90 years of experience, PRINCO process instruments have provided have provided accurate, dependable, long lived service .
Sensitivity
Senses process capacitance changes as low as 0.5 pF.
Operating Temperature
-40 to 150°F (-40 to 66°C).
Relay Contacts
DPDT contacts rated at 10 amperes, 115 VAC or 26 VDC, resistive load.
Delay Time/Mode
0 to 30 second/delay on and off.
Fail-Safe Mode
Fail-Safe low level or high level. Field changeable.